Set up plugins for me: run `claude plugin marketplace add https://archaiflow.com/plugins/marketplace.json` and then `claude plugin install penetration-review@archaiflow`Paste into the Code tab (not Chat or Cowork) and approve when Claude asks. The third-party marketplace it mentions is this site. Windows may ask to install Git once.
What this skill does
Penetration Review
Penetrations are made by five trades who never read each other's drawings, through assemblies drawn by a sixth. Each hole is closed by somebody, to some standard, with a product chosen on site. The register is the only place all of it comes together, and most projects do not have one.
Workflow
Step 1. Establish what has performance to keep
Ask, in one message:
- Which assemblies carry a required performance, and what is it? Fire, smoke, acoustic, structural, air, or several at once.
- Where does each requirement come from? Quote it.
- Which discipline drawings do you have, and at what revision?
- What does the specification say about firestopping: who provides it, to what standard, and whether submittals are required per condition?
- Is there a coordinated model, or are these separate drawings?
An assembly usually carries more than one requirement, and they are closed by different products. A rated wall that is also an acoustic separation needs both, and a firestop that satisfies the rating may not satisfy the acoustic requirement.
Step 2. Build the register, discipline by discipline
Work each discipline's drawings over the assembly plan and log every crossing.
| # | Assembly | Requirements | Penetrant | Discipline | Size | Closure | Listing cited | Status |
|---|
Do not summarise by type. A register saying "all pipe penetrations" is not a register; the listing depends on the pipe's material, size, insulation and the assembly it passes through, and those vary along one wall.
Include the penetrations nobody draws: recessed boxes, back-to-back outlets, control joints, structural connections, anchors, hangers, and anything a specialist trade brings later.
Step 3. Check each one for the three questions together
For every row:
- What performance must be kept? All of the assembly's requirements, not just the fire rating.
- What closes it? A named physical closure. "Firestop" is not a closure; a system is.
- Is there a listing for this exact condition? Penetrant material, size,
insulation, annular space, assembly type, and orientation all have to match.
Mark
cited,not cited, orno known system.
no known system is a real outcome and it means the design has to change. It is
found on site otherwise.
Step 4. Find the ones that only appear across disciplines
The value of doing this in one register:
- Two penetrants too close together. Listings specify minimum separation between penetrations, and two trades each drew a hole without seeing the other.
- Back-to-back penetrations through the same assembly.
- Penetrations clustered enough to compromise the assembly structurally or in aggregate.
- A penetration through a structural element that the structural drawings do not show.
- Something crossing a dedicated space or a clearance zone. Point at
design-electrical-room. - A penetration through an assembly that also carries the air barrier. Point
at
air-barrier-trace.
Step 5. Report
- Counts by status,
no known systemandnot citedfirst. - Cross-discipline conflicts, individually.
- Penetrations of structural elements, listed for the engineer.
- Assemblies where the acoustic requirement was not addressed alongside the fire rating.
- What could not be reviewed: missing discipline drawings, drawings at different revisions, a specification that does not say who provides firestopping.
Close with the standing limits: no listing was verified, and the register records what is drawn rather than what will be built.
Step 6. Save
Ask where. CSV, because the register becomes a submittal checklist and an inspection list.
Rules
- Never supply a listing number, a rating, or an acoustic value.
- Never verify a listing. Record whether one was cited.
- Log every penetration individually. Never summarise by type.
- Record all of an assembly's requirements, not only the fire rating.
- Include the penetrations nobody draws.
- Check separation between adjacent penetrations across disciplines.
- Say plainly when there is no known system.
Anti-patterns
- Reviewing the mechanical drawings and calling it a penetration review.
- Logging "typical pipe penetration" for a run of different pipes.
- Recalling a firestop system number.
- Addressing the fire rating and not the acoustic requirement.
- Missing two penetrations too close together because each discipline was reviewed alone.
- Treating a recessed box as too small to matter.
- Accepting "firestop per specification" as a closure.
- Reviewing drawings at different revisions without saying so.
Resources
None. This skill is one file. The register is written at the path you choose.
What it does not check
What this does. Builds a register of every penetration through every assembly with a performance requirement, and for each one records the required performance, the physical closure, and the listing or test that supports it.
What this does not do.
- It carries no listings, ratings or values. Required fire ratings come from your code analysis; acoustic requirements from the specification or the acoustician; every firestop system is a listed system you cite by number from the listing document.
- It does not verify a listing. Whether a system is listed for that penetrant, that assembly, that annular space and that orientation is checked against the listing itself. This checks whether anyone has cited one.
- It does not cover the assembly's own continuity.
design-fire-barriertraces the surface; this reviews what goes through it. - It does not cover air, water and vapor.
air-barrier-tracedoes, and a penetration usually breaches both, which is why the register notes it. - It does not do structural work. A penetration through a structural element is the engineer's to approve.
- It does not replace the Architect of Record.